Address of Installation |
|
Location of Installation | ||
Installer |
|
Date of Installation | ||
Inspector |
|
Date of Inspection | ||
Please leave a tick for the ones that comply and leave an X for the ones that do not comply. A second time review is required to be performed on the ones with nonconformities. |
||||
Order |
Items to be Inspected and Criteria for Inspection |
Inspection Result and Explanation |
||
1 |
Whether the cover of the bottom u channel is smooth without making any noise (attached with an elastic strip). |
|
||
2 |
Push and pull with hand to check if the screws on the side columns are tightened properly. |
|
||
3 |
Whether the silicone is filled on the back, bottom and sides of the side columns. |
|
||
4 |
Whether the protruding screws tightened on the side columns are sealed with silicone. |
|
||
5 |
Whether the side columns and the central column are perpendicular to the ground level (by checking with level staff). |
|
||
6 |
Whether the waterproof strips on the side columns and the waterproof strip on the central column extended 1 cm into the waterproof strip on the bottom u channel. |
|
||
7 |
Whether the bottoms of the concave waterproof plates between the side columns and central column are on the same level with the bottom u channel (uncover the waterproof strip and check with your finger). |
|
||
8 |
Whether the waterproof gasket at the bottom of the central column can be closely attached to the horizontal wing plates on the bottom u channel. |
|
||
9 |
Whether the pre-embedded bolts on the central column and the diagonal support are properly tightened. |
|
||
10 |
Whether the central column and the diagonal support are smoothly installed (3-point screw drilling tests are performed on the connection between the central column and the diagonal support as well as the diagonal support and the diagonal support base) |
|
||
11 |
Whether the waterproof plates are smoothly installed (where there is a gap of a finger width on both sides). |
|
||
12 |
Whether there is a flooding test with the water level of ( ) cm. |
|
||
13 |
Whether the multi-stage compression lock can be pressed against the waterproof plate at each stage. |
|
||
14 |
Whether the pressing screws of each column can be pressed and released smoothly. |
|
||
15 |
Whether the lower compression strip is less than 15 cm from each column. |
|
||
16 |
Customers are taught to install the waterproof gate every step of the way. |
|
||
Note |
|